Datum
2022-10-18Schlagwort
333 Boden- und Energiewirtschaft ÖsterreichDeutschlandElektrizitätsversorgungsnetzErneuerbare EnergienFrequenzstabilitätEnergiespeicherungStromausfallMetadata
Zur Langanzeige
Aufsatz
Cold Load Pickup Model Adequacy for Power System Restoration Studies
Zusammenfassung
When a grid section is re-energized after an interruption, the load behaviour can be significantly different from normal operation. In this manuscript, the impact of the phenomenon—known as cold load pickup—is investigated by evaluating 31 time series measured after network outages in Austria and Germany. Its impact on power system restoration and the adequacy of the most common type of simplified model for such investigations is assessed by the time domain simulation of a restoration setting involving the parallel operation of conventional and renewable generation. Parameter distributions are provided for the exponential decay and the delayed exponential decay model with the aim of facilitating meaningful consideration of the phenomenon in time domain simulations of power system restoration. The benefits and limitations of these models are assessed by comparison of time domain simulation results using either the normalized raw data, an exponential decay model or a step-wise active power chance to reflect load behaviour. It is shown that using an exponential decay model leads to higher fidelity of simulation results with respect to the resulting steady-state active power sharing among generators than just applying a step-wise power change in the simulation.
Zitierform
In: Energies Volume 15 / Issue 20 (2022-10-18) eissn:1996-1073Förderhinweis
Gefördert durch den Publikationsfonds der Universität KasselZitieren
@article{doi:10.17170/kobra-202210267040,
author={Hachmann, Christian and Becker, Holger and Braun, Martin},
title={Cold Load Pickup Model Adequacy for Power System Restoration Studies},
journal={Energies},
year={2022}
}
0500 Oax 0501 Text $btxt$2rdacontent 0502 Computermedien $bc$2rdacarrier 1100 2022$n2022 1500 1/eng 2050 ##0##http://hdl.handle.net/123456789/14219 3000 Hachmann, Christian 3010 Becker, Holger 3010 Braun, Martin 4000 Cold Load Pickup Model Adequacy for Power System Restoration Studies / Hachmann, Christian 4030 4060 Online-Ressource 4085 ##0##=u http://nbn-resolving.de/http://hdl.handle.net/123456789/14219=x R 4204 \$dAufsatz 4170 5550 {{Österreich}} 5550 {{Deutschland}} 5550 {{Elektrizitätsversorgungsnetz}} 5550 {{Erneuerbare Energien}} 5550 {{Frequenzstabilität}} 5550 {{Energiespeicherung}} 5550 {{Stromausfall}} 7136 ##0##http://hdl.handle.net/123456789/14219
2022-10-27T06:42:14Z 2022-10-27T06:42:14Z 2022-10-18 doi:10.17170/kobra-202210267040 http://hdl.handle.net/123456789/14219 Gefördert durch den Publikationsfonds der Universität Kassel eng Namensnennung 4.0 International http://creativecommons.org/licenses/by/4.0/ cold load pickup power system restoration load modelling thermal loads charging storage frequency stability renewable generation 333 Cold Load Pickup Model Adequacy for Power System Restoration Studies Aufsatz When a grid section is re-energized after an interruption, the load behaviour can be significantly different from normal operation. In this manuscript, the impact of the phenomenon—known as cold load pickup—is investigated by evaluating 31 time series measured after network outages in Austria and Germany. Its impact on power system restoration and the adequacy of the most common type of simplified model for such investigations is assessed by the time domain simulation of a restoration setting involving the parallel operation of conventional and renewable generation. Parameter distributions are provided for the exponential decay and the delayed exponential decay model with the aim of facilitating meaningful consideration of the phenomenon in time domain simulations of power system restoration. The benefits and limitations of these models are assessed by comparison of time domain simulation results using either the normalized raw data, an exponential decay model or a step-wise active power chance to reflect load behaviour. It is shown that using an exponential decay model leads to higher fidelity of simulation results with respect to the resulting steady-state active power sharing among generators than just applying a step-wise power change in the simulation. open access Hachmann, Christian Becker, Holger Braun, Martin doi:10.3390/en15207675 Österreich Deutschland Elektrizitätsversorgungsnetz Erneuerbare Energien Frequenzstabilität Energiespeicherung Stromausfall publishedVersion eissn:1996-1073 Issue 20 Energies Volume 15 false 7675